- Capacity
- 20kVA
- Load Capacity
- 20kW
- Input Voltage
- 3 x 400VAC (3Ph+N) / 230VAC (1Ph+N)
- Output Voltage
- 3 x 360*/380*/400/415 VAC (3Ph+N)
- Frequency (Battery Mode)
- 50Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
- Others
- Output Harmonic Distortion (THDi): ≤2% THD (Linear Load) ; ≤5 % THD (Non-linear Load) Output Overload Capability: 100 – 110% for 60min, 111 – 125% for 10min, 126% – 150% 1min, >150% immediately Input Harmonic Distortion (THDi): <4% at full linear loa
- Frequency
- 46 – 54Hz @ 50Hz system; 56 – 64Hz @ 60Hz system
- Power Factor
- ≥0.99 @ 100% Load
- Voltage Range
- 110 – 300VAC ± 3 % @ 50% load; 176 – 276VAC ± 3 % @ 100% load
- Type of Wave
- Pure Sine wave
- Transfer Time
- AC Mode to Batt. Mode: 0ms Inverter to Bypass: 0ms